Page 3 - Crown Head Owners Manual L91v0116v
P. 3
Crown Head with Raritan Sanitation Device, Crown Head with Raritan Sanitation Device
FIG 2 Holding Tank and “Y” Valve FIG 3 and Vented Loops
To
Deck
Pumpout Vented Vented Loop
Loop
Crown Head Crown Head
“Y” Valve Holding Tank
Sanitation Device Discharge
Intake Thru-Hull
Thru-Hull and And Seacock
Seacock
Sanitation Device Drawing Not to Scale
Intake Discharge At or Below Waterline Installation Shown
Thru-Hull Thru-Hull
and Seacock and Seacock
Drawing Not to Scale 3. Connect ground wire from the battery or power source
Above Waterline Installation Shown
PLUMBING to the negative terminal on the motor.
WARNING: HAZARD OF FLOODING For VAC 120/240 Crown Head Units: See
Toilets mounted at or below the waterline, at greatest instructions with transformer units.
angle of heel, and connected to a Seacock/Thru Hull SYSTEM START-UP
Fitting(s) MUST have VENTED LOOPS installed
in toilet discharge plumbing and between raw water 1. Be sure intake and discharge seacocks are open.
intake pump and toilet bowl. 2. Remove the cap from the Concentrate reservoir
Install vented loops per manufacturer’s instructions. and pour in 2 oz. (59ml) of Concentrate; fill the
Double clamp all below-waterline connections. remainder of the reservoir with fresh water and
Whenever possible hose connections should be secured replace the cap and siphon assembly.
using two all-stainless steel hose clamps. Integrity of
clamps, hoses and fittings should be checked periodically. 3. Refer to Operation on page 1. If the toilet does not
Fittings and 90 degree bends should be kept to a minimum flush properly, or if water does not enter the bowl
to maintain proper performance. within 10 seconds, refer to the Troubleshooting
NOTE: Discharge of raw untreated sewage is Section. Running the unit dry will damage the
restricted in all U. S. waters inside the three-mile limit. intake pump.
“Y” Valves, if installed, must direct toilet discharge to
a USCG approved treatment system or holding tank
and must be secured in that position while inside the FIG 4 Pushbutton
Switch
three-mile limit. (164000BR) 3 Amp Fuse or
Circuit Breaker
WIRING #14 Awg Main Fuse or
Circuit Breaker
WARNING: RISK OF FIRE - The Crown Head must Wire (See Specification Chart)
be wired to a separately fused circuit with no other
electrical appliances on the circuit. Pos Voltage from
Battery or DC Power
1. Measure wire distance from power source to toilet Panel
and back, refer to Specification Table for proper wire Solenoid Relay Battery
gauge and circuit breaker/fuse sizes. (CDS) Lug
12, 24 and 32 VDC Crown Head Units: Wire as per
FIG 4. (For momentary push button switch operation.) + (Pos)
2. Using a protected circuit that is appropriate for the Crown Head
voltage of the unit, connect the positive lead from - (Neg)
the battery or power source to the “BAT” lug on the Wiring the Crown Head (DC Unit with
relay and connect a lead from the other relay lug to Ground Momentary Push Button Switch
the positive terminal on the Crown Head motor.
3
L91 0116jlc